Model Programming Choices
1F95-1280
7 Day 5/1/1 Day Non-Programmable
www.white-rodgers.com
Big Blue Commercial Universal Thermostat
with Damper or Economizer Control and
Automatic Heat/Cool Changeover Option
PART NO. 37-6978A
0832
Single Stage, Multi-Stage, Heat Pump
Installation and Operating Instructions
APPLICATIONS
1F95-1280 Commercial Touchscreen Thermostat
SPECIFICATIONS
Electrical Rating:
Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . mV to 30 VAC, NEC Class II, 50/60 Hz or DC
Input-Hardwire . . . . . . . . . . . . . . . . . . . . . . . . . 20 to 30 VAC
Terminal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5A per terminal, 2.5A maximum all terminals combined
Setpoint Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 to 99°F (7 to 32°C)
Differential (Single Stage) . . . . . . . . . . . . . . . . . . . . Heat 0.6°F; Cool 1.2°F
Differential (Multi-Stage) . . . . . . . . . . . . . . . . . . . . . Heat 0.6°F; Cool 1.2°F
Differential (Heat Pump) . . . . . . . . . . . . . . . . . . . . . Heat 1.2°F; Cool 1.5°F
Operating Ambient. . . . . . . . . . . . . . . . . . . . . . . . . . 32°F to +105°F (0 to +41°C)
Operating Humidity . . . . . . . . . . . . . . . . . . . . . . . . . 90% non-condensing max.
Shipping Temperature Range . . . . . . . . . . . . . . . . . -40 to +150°F (-40 to +65°C)
Dimensions Thermostat. . . . . . . . . . . . . . . . . . . . . . 4.6"H x 5.9"W x 1.2"D
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
CAUTION
!
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
CAREFULLY BEFORE INSTALLING OR OPERATING THIS
CONTROL COULD CAUSE PERSONAL INJURY AND/OR
PROPERTY DAMAGE.
THERMOSTAT APPLICATION GUIDE
Thermostat
Confi guration
Options
Thermostat
Applications
Maximum
Stages
Heat/Cool
W/ Economizer
Max. Stage
Heat/Cool
Single Stage 1
No Heat Pump (SS1)
Gas, Oil, Electric, Heat Only,
Cool Only or Heat/Cool
Systems, 2 or 3 wire Hydronic
Zone (Hot Water or Steam)
Systems, 24 Volt or Millivolt
1/1 1/2
Multi Stage 2
No Heat Pump (MS2)
2/2 2/3
Heat Pump 1
Single Stage
Compressor Heat
Pump (HP1)
Single Stage Compressor Heat
Pump Systems - up to 2 Stages
Aux./Emergency Heat
3/1 3/2
Heat Pump 2
Two Stage or Two
Compressor Heat
Pump (HP2)
Two Stage or Two Compressor
Heat Pump systems - up to 2
Stages Aux./Emergency Heat
4/2 4/3
ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this prod-
uct may replace a product that contains mercury.
Mercury and products containing mercury must not be
discarded in household trash. Do not touch any spilled
mercury. Wearing non-absorbent gloves, clean up any
spilled mercury and place in a sealed container. For proper
disposal of a product containing mercury or a sealed
container of spilled mercury, place it in a suitable shipping
container. Refer to www.white-rodgers.com for location to
send the product containing mercury.
Index Page
Installation 2
Wiring Diagrams 3
Thermostat Quick Reference 4
Installer Confi guration Menu 5
Operating Your Thermostat 9
Programming 10
Troubleshooting 14
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - SPECIFICATIONS

Model Programming Choices1F95-12807 Day 5/1/1 Day Non-Programmablewww.white-rodgers.comBig Blue Commercial Universal Thermostat with Damper or Economi

Page 2 - INSTALLATION

10Program Override (Temporary Override)Press or keys to adjust the temperature. This will over-ride the temperature setting for a (default) four h

Page 3 - WIRING DIAGRAMS

11PROGRAMMINGEnergy Saving Factory Pre-ProgramThe 1F95-1280 thermostats are programmed with the energy saving settings shown in the table below for al

Page 4 - THERMOSTAT QUICK REFERENCE

12PROGRAMMINGCoolingProgramDay (occupied) Night (unoccupied)Fan FanMON6:00 AM 75°F Auto 10:00 PM 78°F AutoTUEWEDTHUFRISAT6:00 AM 75°F Auto 10:00 PM 78

Page 5 - INSTALLER/CONFIGURATION MENU

13PROGRAMMINGWired Remote Temperature SensingOne remote temperature sensor can be installed indoor or outdoor and connected to the thermostat by a max

Page 6

14TROUBLESHOOTINGSymptom Possible Cause Corrective ActionNo Heat/No Cool/No Fan(common problems)1. Blown fuse or tripped circuit breaker.2. Furnace po

Page 7

15NOTES

Page 8

www.white-rodgers.comWhite-Rodgers is a divisionof Emerson Electric Co.The Emerson logo is a trademark and service markof Emerson Electric Co.HOMEOWNE

Page 9

2Remove Old ThermostatBefore removing wires from old thermostat, mark wires for terminal identifi cation so the proper connections will be made to the

Page 10 - PROGRAMMING

3WIRING DIAGRAMSFigure 2 – Single Stage or Multi-Stage System(No Heat Pump) with Single TransformerFigure 3 – Heat Pump SystemsHeat Pump ConnectionsIf

Page 11

4Programming and Confi guration Items 1 Displays and "Keypad Lockout" when in keypadlockout mode.Displays and "Temperature Limit"

Page 12

5INSTALLER/CONFIGURATION MENUTo enter the menu: Press the Menu touch key. Press and hold for 5 seconds the Installer Confi g touch key. This displays m

Page 13

6INSTALLER/CONFIGURATION MENU1. This control can be confi gured for: MS2 – Multi-Stage System - No Heat Pump (2 heat/2 cool) HP1 – Heat Pump with on

Page 14 - TROUBLESHOOTING

714. Select °F or °C Readout – Changes the display readout to Celsius or Fahrenheit as required.15. Select Audio Prompting (Beeper) On or Off – Fact

Page 15

8 Select DF setting (dF) – With DF selected On and no outdoor sensor, select the DF setting from 01-09. Factory default is 05. The thermostat compute

Page 16 - The Emerson logo is a

9OPERATING YOUR THERMOSTATIf at any time during testing your system does not operate properly, contact a qualifi ed service person.Fan OperationIf your