Model Programming Choices1F95-12807 Day 5/1/1 Day Non-Programmablewww.white-rodgers.comBig Blue Commercial Universal Thermostat with Damper or Economi
10Program Override (Temporary Override)Press or keys to adjust the temperature. This will over-ride the temperature setting for a (default) four h
11PROGRAMMINGEnergy Saving Factory Pre-ProgramThe 1F95-1280 thermostats are programmed with the energy saving settings shown in the table below for al
12PROGRAMMINGCoolingProgramDay (occupied) Night (unoccupied)Fan FanMON6:00 AM 75°F Auto 10:00 PM 78°F AutoTUEWEDTHUFRISAT6:00 AM 75°F Auto 10:00 PM 78
13PROGRAMMINGWired Remote Temperature SensingOne remote temperature sensor can be installed indoor or outdoor and connected to the thermostat by a max
14TROUBLESHOOTINGSymptom Possible Cause Corrective ActionNo Heat/No Cool/No Fan(common problems)1. Blown fuse or tripped circuit breaker.2. Furnace po
15NOTES
www.white-rodgers.comWhite-Rodgers is a divisionof Emerson Electric Co.The Emerson logo is a trademark and service markof Emerson Electric Co.HOMEOWNE
2Remove Old ThermostatBefore removing wires from old thermostat, mark wires for terminal identifi cation so the proper connections will be made to the
3WIRING DIAGRAMSFigure 2 – Single Stage or Multi-Stage System(No Heat Pump) with Single TransformerFigure 3 – Heat Pump SystemsHeat Pump ConnectionsIf
4Programming and Confi guration Items 1 Displays and "Keypad Lockout" when in keypadlockout mode.Displays and "Temperature Limit"
5INSTALLER/CONFIGURATION MENUTo enter the menu: Press the Menu touch key. Press and hold for 5 seconds the Installer Confi g touch key. This displays m
6INSTALLER/CONFIGURATION MENU1. This control can be confi gured for: MS2 – Multi-Stage System - No Heat Pump (2 heat/2 cool) HP1 – Heat Pump with on
714. Select °F or °C Readout – Changes the display readout to Celsius or Fahrenheit as required.15. Select Audio Prompting (Beeper) On or Off – Fact
8 Select DF setting (dF) – With DF selected On and no outdoor sensor, select the DF setting from 01-09. Factory default is 05. The thermostat compute
9OPERATING YOUR THERMOSTATIf at any time during testing your system does not operate properly, contact a qualifi ed service person.Fan OperationIf your