Model
Number Pre-Purge
Ignitor
Warm-Up Retries
Heat
Delay to
Fan ON
Heat Delay
to Fan OFF
Cool
Delay to
Fan ON
Cool
Delay to
Fan OFF
Automatic
Reset
Time
21V51U-843 15 17 2 45 90/120/150/180 5 60 60 minutes
?
PAGES
181–182
21V51U-843
Includes:
•Module
•HotRod
Ignitor Kit
•WiringHarness
21V51U-843 UNIVERSAL INTEGRATED
HSI FURNACE CONTROL KIT
Replaces White-Rodgers 50V51-XXX's and 50V61-XXX's
Two-Stage HSI Systems with 80V or 120V Ignitors
FEATURES
•16-pinvariablespeedcirculatoroutputforECM(ElectronicallyCommutatedMotor),
dipswitch selectable for OEM applications two-speed inducer output, two-stage gas
valve output.
•Pushbuttonfaulthistoryretrieval.
•FurnacestatusLED–tri-color(green,redandamber).
•Heatfanoffdelay(dipswitchselectable),fanondelayforcooling.
•Autosecondstagedelay(dipswitchselectable).
•120VAChumidieroutput/120VACelectronicaircleaneroutput.
SPECIFICATIONS
Electrical Rating:
Input Voltage.................... 24 VAC, 60 Hz (Class II transformer required)
Nom. Input Current @ 24 VAC ...... 595mA+MV
Relay Load Ratings:
Gas Valve Relays ................ 1.5 amps @ 24 VAC, 60 Hz
Inducer Relays . . . . . . . . . . . . . . . . . . 2.2 FLA – 3.5 LRA @ 120 VAC
HumidierLoad ................. 1.0 amp max. @ 120 VAC
Electronic Air Cleaner Load ........ 1.0 amp max. @ 120 VAC
Ignitor Relay .................... 4.0 amps max. @ 132 VAC, 60 Hz
Flame Current Requirements:
Minimumcurrenttoinsureamedetection 0.3 µa DC*
Maximum current for non-detection .. 0.1 µa DC*
Maximumallowableleakageresistance100Mohms
*Measured with a DC microameter in the flame probe lead
Operating Temperature Range...... -40
o
to 175
o
F (-40 to 80
o
C)
Humidity Range ................. 5% to 93% relative humidity (non-condensing)
Flame Failure Response Time . . . . . . 2.0 sec. max. @ 60Hz
TECHNICAL HELP
Wiring Diagram/Operation .............. See pages 181–182
UNIVERSAL
REPLACEMENT
TWO-STAGE INTEGRATED
VARIABLE SPEED (ECM)
HSI FURNACE CONTROL
CROSS REFERENCE
18M9901 21V51U-843
20300002 21V51U-843
20300004 21V51U-843
20300006 21V51U-843
20300006S 21V51U-843
21V51U-843 21V51U-843
49M5901 21V51U-843
50V51-243 21V51U-843
50V51-288 21V51U-843
50V51-289 21V51U-843
50V51-290 21V51U-843
50V51-507 21V51U-843
50V61-120 21V51U-843
50V61-143 21V51U-843
50V61-288 21V51U-843
50V61-289 21V51U-843
50V61-480 21V51U-843
50V61-486 21V51U-843
50V61-507 21V51U-843
B1809925 21V51U-843
B1809927 21V51U-843
B1809927S 21V51U-843
CNT 04018 21V51U-843
CNT 04352 21V51U-843
CNT03078 21V51U-843
D156245P01 21V51U-843
D34142P01 21V51U-843
PCB00106 21V51U-843
PCB00106S 21V51U-843
PCBBF106 21V51U-843
PCBBF106S 21V51U-843
PCBBF107S 21V51U-843
X13650840010 21V51U-843
21V51U-843 Replaces:
www.white-rodgers.com
46
HEATING
Page view 0
1

Summary of Contents

Page 1 - REPLACEMENT

Model Number Pre-PurgeIgnitor Warm-Up RetriesHeat Delay to Fan ONHeat Delay to Fan OFFCool Delay to Fan ONCool Delay to Fan OFFAutomaticResetTime21V51

Comments to this Manuals

No comments