Model Programming Choices
1F95-1280
7 Day 5/1/1 Day Non-Programmable
Big Blue Commercial Universal Thermostat
with Damper or Economizer Control and
Automatic Heat/Cool Changeover Option
Single Stage, Multi-Stage, Heat Pump
Installation and Operating Instructions
APPLICATIONS
1F95-1280
SPECIFICATIONS
Electrical Rating:
Battery Power .......................... mV to 30 VAC, NEC Class II, 50/60 Hz or DC
Input-Hardwire ......................... 20 to 30 VAC
Terminal Load ............................. 1.5A per terminal, 2.5A maximum all terminals combined
Setpoint Range ............................ 45 to 99°F (7 to 37°C)
Rated Differentials: Fast Slow
Heat (SS1, MS2) ....................... 0.6°F 1.5°F
Cool (SS1, MS2)........................ 1.2°F 1.7°F
Heat Pump (HP1, HP2) .................. 1.2°F 1.7°F
Emer Heat (HP1, HP2) ................... 0.6°F 1.7°F
Operating Ambient.......................... 32°F to +105°F (0 to +41°C)
Operating Humidity ......................... 90% non-condensing max.
Shipping Temperature Range ................. -40 to +150°F (-40 to +65°C)
Dimensions Thermostat...................... 4-9/16"H x 5-13/16"W x 1-3/16"D
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
CAUTION
!
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
CAREFULLY BEFORE INSTALLING OR OPERATING THIS
CONTROL COULD CAUSE PERSONAL INJURY AND/OR
PROPERTY DAMAGE.
THERMOSTAT APPLICATION GUIDE
Thermostat
Configuration
Options
Thermostat
Applications
Maximum
Stages
Heat/Cool
W/ Economizer
Max. Stage
Heat/Cool
Single Stage 1
No Heat Pump (SS1)
Gas, Oil, Electric, Heat Only,
Cool Only or Heat/Cool
Systems, 2 or 3 wire Hydronic
Zone (Hot Water or Steam)
Systems, 24 Volt or Millivolt
1/1 1/2
Multi Stage 2
No Heat Pump (MS2)
2/2 2/3
Heat Pump 1
Single Stage
Compressor Heat
Pump (HP1)
Single Stage Compressor Heat
Pump Systems - up to 2 Stages
Aux./Emergency Heat
3/1 3/2
Heat Pump 2
Two Stage or Two
Compressor Heat
Pump (HP2)
Two Stage or Two Compressor
Heat Pump systems - up to 2
Stages Aux./Emergency Heat
4/2 4/3
ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this prod-
uct may replace a product that contains mercury.
Mercury and products containing mercury must not be
discarded in household trash. Do not touch any spilled mer-
cury. Wearing non-absorbent gloves, clean up any spilled
mercury and place in a sealed container. For proper disposal
of a product containing mercury or a sealed container of
spilled mercury, place it in a suitable shipping container.
Refer to www.thermostat-recycle.org for location to send
the product containing mercury.
Index Page
Installation 2
Wiring Diagrams 3
Thermostat Quick Reference 4
Installer Configuration Menu 5
Operating Your Thermostat 9
Programming 10
Troubleshooting 14
www.white-rodgers.com
www.emersonclimate.com
PART NO. 37-7292A
Replaces 37-6978C
1134
Page view 0
1 2 3 4 5 6 ... 15 16

Summary of Contents

Page 1 - SPECIFICATIONS

Model Programming Choices1F95-12807 Day 5/1/1 Day Non-ProgrammableBig Blue Commercial Universal Thermostat with Damper or Economizer Control and Autom

Page 2 - INSTALLATION

Program Override (Temporary Override)Press or keys to adjust the temperature. This will over-ride the temperature setting for a (default) four hou

Page 3 - WIRING DIAGRAMS

PROGRAMMINGEnergy Saving Factory Pre-ProgramThe 1F95-1280 thermostats are programmed with the energy saving settings shown in the table below for all

Page 4 - THERMOSTAT QUICK REFERENCE

PROGRAMMINGCoolingProgramDay (occupied) Night (unoccupied)Fan FanMON6:00 AM 75°F Auto 10:00 PM 78°F AutoTUEWEDTHUFRISAT6:00 AM 75°F Auto 10:00 PM 78°F

Page 5 - INSTALLER/CONFIGURATION MENU

PROGRAMMINGWired Remote Temperature SensingOne remote temperature sensor can be installed indoor or outdoor and connected to the thermostat by a maxim

Page 6

TROUBLESHOOTINGSymptom Possible Cause Corrective ActionNo Heat/No Cool/No Fan (common problems)1. Blown fuse or tripped circuit breaker. 2. Furnace po

Page 7

15NOTES

Page 8

White-Rodgers is a division of Emerson Electric Co.The Emerson logo is a trademark and service mark of Emerson Electric Co.HOMEOWNER HELP LINE: 1-80

Page 9

Remove Old ThermostatBefore removing wires from old thermostat, mark wires for terminal identification so the proper connections will be made to the ne

Page 10 - PROGRAMMING

WIRING DIAGRAMSFigure 2 – Single Stage or Multi-Stage System(No Heat Pump) with Single TransformerFigure 3 – Heat Pump SystemsHeat Pump ConnectionsIf

Page 11

Programming and Configuration Items 1 Displays and "Keypad Lockout" when in keypad lockout mode. Displays and "Temperature Limit"

Page 12

INSTALLER/CONFIGURATION MENUTo enter the menu: Press the Menu touch key. Press and hold for 5 seconds the Installer Config touch key. This displays scr

Page 13

INSTALLER/CONFIGURATION MENU1. This control can be configured for: MS2 – Multi-Stage System - No Heat Pump (2 heat/2 cool) HP1 – Heat Pump with one

Page 14 - TROUBLESHOOTING

14. Select °F or °C Readout – Changes the display readout to Celsius or Fahrenheit as required.15. Select Audio Prompting (Beeper) On or Off – Facto

Page 15

The Fast Cool feature operates the cooling stages in the same manner as Fast Heat, On or Off when the tempera-ture is lowered below the room setting

Page 16 - The Emerson logo is a

OPERATING YOUR THERMOSTATIf at any time during testing your system does not operate properly, contact a qualified service person.Fan OperationIf your s