Printed in U.S.A.
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300, FAX (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
These room thermostats have been designed for control-
ling cooling equipment operating on line voltage with
heavy electrical loads. They are suitable for operation of
unit coolers, room coolers, etc., or any similar refrigera-
tion application requiring a heavy duty room thermostat.
Models are available with various ranges for meeting the
needs of almost any application.
PRECAUTIONS
THESE CONTROLS MUST BE INSTALLED BY A
QUALIFIED INSTALLER.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
This control has been accurately calibrated at the factory.
Any attempt to calibrate this control will void the White-
Rodgers warranty.
To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.
Do not use on circuits exceeding specified volt-
ages. Higher voltages will damage control and
could cause shock or fire hazard.
WARNING
INSTALLATION
CONCRETE
PLASTER
JUNCTION BOX
THERMOSTAT
CONDUIT
ALONG WALL
CONDUIT
INSIDE WALL
WALL INSTALLATION
The mounting plate for this thermostat has two
holes 3
5
/
16
”apart for attaching the control on a
standard switch box.
TYPE 151
ROOM THERMOSTAT
Cooling Service, External Dial
INSTALLATION INSTRUCTIONS
The proper location of a heavy duty room thermostat is
very important to assure good performance. The following
general rules will help in determining the proper location:
1. Make sure that it is in a place where air circulates
around it freely. This is important.
2. Never install it on or near an outside wall.
3. Keep it away from windows or doors.
4. Don’t locate it too close to a strong light or any other
false source of heat such as direct sunlight, steam
lines, etc.
5. Mount it on a post or a partitioning wall, but make sure
that there are no pipes or duct work in that wall or
directly behind it.
6. If the electrical conduit leads into a cooler or a warmer
room, plug up the space around the wires in the conduit
with rock wool.
Figure 1
WHITE-RODGERS
Operator: Save these instructions for future use!
90
80
70
60
50
40
W
H
I
T
E
-
R
O
D
G
E
R
S
PART NO. 37-1118B
Replaces 37-1118
9548
Comments to this Manuals