THERMOSTATS
LINE VOLTAGE
THERMOSTATS
201-8
179-1
HEAVY DUTY SPACE THERMOSTATS FOR COOLING
Designed for Use in Garages, Factories, Warehouses and Similar
Commercial and Industrial Installations
FEATURES
•Dust,moistureandverminresistantheavymetalcase.
•Nolevelingrequired–Mountsinanyposition.
•Quickresponsetotemperaturechanges.
•Nickelplatedelement.
•Extraruggedswitchmechanism.
SPECIFICATIONS
Dimensions............................. 5
3
/
8
H x 2
1
/
2
W x 2
5
/
16
D (Vertical)
Finish ................................. Grey Color
Agency ................................ U.L. listed and C.S.A. approved
LINE VOLTAGE THERMOSTAT FOR HEATING / COOLING
Control Suitable for Fans or Water Solenoids on Heating / Cooling
Convectors or Any Similar Application that Requires a Heavy Duty
Room Thermostat with Single Pole, Double Throw (SPDT) Switch Action
FEATURES
•Canhandlemanycoolinginstallationswithoutuseofrelayormotorstarter.
•Heavygaugesteelcase–Mountsonvertical2 x 4boxorustowall.
•Hydraulicactionelement–Unaffectedbymotion–Nolevelingrequired.
•Dustproofcase.
SPECIFICATIONS
Dimensions............................. 6H x 2
3
/
4
W x 2
1
/
2
D
Finish ................................. Grey Color
Agency ................................ U.L. listed and C.S.A. approved
PARTS AND ACCESSORIES See end of thermostats section for additional parts and accessories
•ThermostatGuards—seepages34–35
Model
Number Range Differential System Action
Full Electrical
Rating
Bulb
Size
Capillary
Length
Motor Rating
(Full Load)
Resistive
(Non-Inductive)
120 VAC 240 VAC 120 VAC 240 VAC
201-8
20 to 90°F
(-7 to 32°C)
Adj. 3 to 20°F
(2 to 11°C) Close on Rise
FGH
See page 222 16.0A 8.0A 5.6A 2.8A 25.0A 22.0A
Model
Number Range Differential Action
Full Electrical
Rating
Motor Rating
(Full Load)
120 VAC 240 VAC
179-1
55 to 95°F
(13 to 35°C)
Fixed 3.0°F
(1.6°C)
SPDT
(Heat / Cool)
SPDT
See page 222 7.4A 3.7
www.white-rodgers.com