6
INSTALLER/CONFIGURATION MENU
To enter the menu: Press the Menu touch key. Press and hold for 5 seconds the Installer Config touch key. This displays
menu item #1 in the table below. Press
to advance to the next menu item or to return to a previous menu item. Press
or
to change a menu item option.
CONFIGURATION MENU
Menu
Reference
Number
Program-
mable
Non-
Program-
mable
Press
key
Displayed
Factory
(Default)
Press
or
to select from
listed options
Comments
1 1 1 MS 2 HP 1, HP 2, SS 1 Selects Multi-Stage (MS2, No Heat Pump), Heat Pump 1
(HP1, 1 compressor), Heat Pump 2 (HP2, 2 compressor
or 2 speed compressor), or Single Stage.
2 2 2
GAS (ELE) GAS setting: furnace controls blower.
ELE setting: thermostat controls blower.
3 3 3
ob (O) b Selects Reversing Valve (This item is only to appear if HP1 or HP2 is
selected above.)
4 4 3
Days, (7) P 5 or 0 Programs per week. (5=5-1-1 or 0 = non-programmable)
5 5 NA
PS (4) 2
Programs per day.
4 = Morning, Day, Evening, Night
2 = Day, Night
6 6 4
Cool-Off-
Heat-Auto
Cool-Off-Heat, Heat Off,
Heat, Cool-Off, Auto Off
System switch configuration in non heat pump mode.
Cool-Off-Heat-
Em-Auto
Cool-Off-Heat-Em,
Off-Em-Auto
System switch configuration, heat pump mode.
7 7 NA
E (On)
OFF
Selects Energy Management Recovery, E (with programming option on)
8 8 5 Cr, Heat (FA) SL Selects Adjustable Anticipation, cycle rate, Heat
9 9 6
Cr, Cool (FA) SL Selects Adjustable Anticipation, cycle rate, Cool
10 10 7
Cr/AU, Em (FA) SL Selects Adjustable Anticipation, cycle rate auxiliary, (This item is
only to appear if HP1 or HP2 is selected above).
11 11 8
CL (OFF) On Selects Compressor Lockout.
12 12 9
dL (On) OFF Selects Continuous Display backlight.
13 13 10
dL (LO) HI Selects Backlight Intensity.
14 14 11
0
(Temperature)
5, LO to 5, HI Selects Adjustable Ambient Temperature Display [range -5 (LO) to
+5 (HI)].
15 15 12
°F °C
Selects °F/°C Display (temperature units in Fahrenheit or Celsius).
16 16 13
b (On) OFF Selects audible Beeper On/Off.
17 17 14
dS (On) OFF Selects Daylight Saving Time calculation.
18 18 15 AS, Heat (On) OFF Selects Automatic Schedule for comfort temperature Programming,
heat mode.
19 19 16
AS, Cool (On) OFF Selects Automatic Schedule for comfort temperature Programming,
cool mode.
20 20 17
CS, (OFF) On Selects Cool Savings Feature On of Off.
CS Cool Savings
(3)
1-2-3-4-5-6 Selects amount of Cool Savings adjustment.
21 21 18
CO (Off) On Select Compressor Optimization (not available on earlier models)
22 22 19 HL, Heat (99) 62-98 TEMPERATURE LIMIT, HEAT (max. heat set point).
23 23 20 LL, Cool (45) 46-82 TEMPERATURE LIMIT, COOL (min. cool set point).
24 24 21
OFF,
Keypad Lockout
L (total), P (partial),
Temperature Limit
(limited temperature range)
Selects Keypad Lockout.
000 001-999 Selects Keypad Lockout Combination (active only if keypad Lockout
is selected).
25 25 22
FS, Heat (On) OFF Fast second stage of heat (not available if SS1 is selected above).
26 26 23 FS, Cool (On) OFF Fast second stage of cool (not available if SS1 or HP1 is selected
above).
27 27 24
Remote (OFF) On Remote temperature sensor, enable/disable.
In, Remote Outdoor Remote Remote temperature sensor (Indoor/Outdoor).
LS (On) OFF Local temp. Sensor enable/disable (only when Indoor Remote is
selected On).
28 28 25
dF (OFF) On Selects Dual Fuel feature using software logic On or OFF (This item
appears if HP1 or HP2 is selected above and no outdoor sensor.
dF (05) 0-09 Selects Dual Fuel setpoint (°F) with no outdoor sensor.
Cd (60) 0-99 Selects compressor delay in seconds.
29 29 26
dF (OFF) On Selects Dual Fuel feature using outdoor sensor On or OFF (This item
appears if HP1 or HP2 is selected and outdoor sensor is installed and
enabled.