92-21354-54-03
SUPERSEDES 92-21354-54-02
PACKAGE AIR CONDITIONERS
FEATURING EARTH-FRIENDLY R-410A REFRIGERANT:
RSNL- 13 SEER (2-5 TONS)
RSPL- 14 SEER (2-5 TONS)
INSTALLATION INSTRUCTIONS
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!
!
DO NOT DESTROY THIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO
QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER
INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT.
READ THESE INSTRUCTIONS THOROUGHLY BEFORE
ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOL-
LOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER
INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE
POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK,
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
[ ] INDICATES METRIC CONVERSIONS
ISO 9001:2000
ISO 9001:2000
refrigerant
(14 SEER ONLY)
Page view 0
1 2 3 4 5 6 ... 51 52

Summary of Contents

Page 1 - INSTALLATION INSTRUCTIONS

92-21354-54-03SUPERSEDES 92-21354-54-02PACKAGE AIR CONDITIONERSFEATURING EARTH-FRIENDLY R-410A REFRIGERANT:RSNL- 13 SEER (2-5 TONS)RSPL- 14 SEER (2-5

Page 2 - TABLE OF CONTENTS

10FIGURE 4UNIT DIMENSIONS BLOWER/EVAPORATORACCESS PANELELECTRICALPOWERENTRANCESIDE SUPPLYDUCT OPENINGOUTDOOR FAN GRILLEAND COMPRESSOR ACCESSCONTROLACC

Page 3 - I. SAFETY INFORMATION

11IMPORTANT: Unit must be level to prevent water migration.FIGURE 4 (continued)UNIT DIMENSIONS Model # Height “A”B024, B030,B0363515⁄16"41"

Page 4 - IV. SPECIFICATIONS

12VI. INSTALLATIONA. GENERAL1. PRE-INSTALLATION CHECK-POINTSBefore attempting any installation, the following points should be carefully consid-ered:a

Page 5 - 1. Comfort Alert™

FIGURE 5PACKAGE AIR CONDITIONER – OUTSIDE SLAB INSTALLATION,BASEMENT OR CRAWL SPACE DISTRIBUTION SYSTEM.FIGURE 6PACKAGE AIR CONDITIONER – OUTSIDE SLAB

Page 6 - 3. Low Pressure Control (LPC)

14VII.DUCTWORKDuctwork should be fabricated by the installing contractor in accordance with local codesand NFPA90A. Industry manuals may be used as a

Page 7

15VIII.FILTERSFilters are not provided with this unit. They may be supplied and installed in the returnair duct by the installer. A field installed fi

Page 8

16IX. CONVERSION PROCEDURE1. HORIZONTAL TO DOWNFLOWa. Remove screws and covers from the downflow supply and return sections. Bothcovers are accessibl

Page 9 - IV. (Corrosive Environment)

17XI. ELECTRICAL WIRINGField wiring must comply with the National Electrical Code* and local ordinances that mayapply.*C.E.C. in CanadaA. POWER WIRING

Page 10 - % OF TOTAL UNIT

18c. Clean and recoat aluminum conductor with inhibitor.d. Make the splice using the above listed wire nuts or split bolt connectors.e. Coat the entir

Page 11 - IGURE 4 (continued)

19E. GROUNDINGGROUNDING MAY ALSO BE ACCOMPLISHED BY GROUNDING THE POWERLINE CONDUIT TO THE UNIT. MAKE SURE THE CONDUIT NUT LOCKING TEETHHAVE P

Page 12 - VI. INSTALLATION

2TABLE OF CONTENTSI. Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3II. Introduct

Page 13 - FIGURE 7

20XV. STARTUP1. Turn thermostat to “OFF,” turn “on” power supply at disconnect switch.2. Turn temperature setting as high as it will go.3. Turn fan sw

Page 14 - VII.DUCTWORK

XVII. AUXILIARY HEATA. CONTROL SYSTEM OPERATION1. In the cooling mode, the thermostat will, on a call for cooling, energize the com-pressor contactor

Page 15 - VIII.FILTERS

22XIX. GENERAL DATA - RSNL- MODELSNOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSNL- Series B024JK B030JK B036CK B036JKCooling Performanc

Page 16 - X. CONDENSATE DRAIN

23GENERAL DATA - RSNL- MODELSNOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSNL- Series B042CK B042JK B048CK B048JKCooling Performance1Conti

Page 17 - XI. ELECTRICAL WIRING

24GENERAL DATA - RSNL- MODELSNOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSNL- Series B060CK B060JKCooling Performance1 Gross Cooling Cap

Page 18 - D. INTERNAL WIRING

25GENERAL DATA - RSPL- MODELSNOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSPL- Series B024JK B030JK B036CK B036JKCooling Performance1Conti

Page 19 - XIV.PRE-START CHECK

26GENERAL DATA - RSPL- MODELSNOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSPL- Series B042CK B042JK B048CK B048JKCooling Performance1Conti

Page 20 - XVI. OPERATION

27GENERAL DATA - RSPL- MODELSNOMINAL SIZES 2-5 TONS [7-17.6 kW] Model RSPL- Series B060CK B060JKCooling Performance1 Gross Cooling Cap

Page 21 - XVII. AUXILIARY HEAT

28XX. ELECTRICAL DATA187-253 187-253 187-253 187-253 187-253 187-253 187-253 187-253 197-253 197-25319/19 22/22 17/17 25/25 22/22 27/27 24/24 34/34 32

Page 22 -

29INDOOR AIRFLOW PERFORMANCE FOR 2-5 TON PACKAGE AIR CONDITIONER: RSNL-DIRECT DRIVE0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.1

Page 23 - GENERAL DATA - RSNL- MODELS

3I. SAFETY INFORMATION!WARNINGPROPOSITION 65: THIS APPLIANCE CONTAINS FIBERGLASS INSULATION.RESPIRABLE PARTICLES OF FIBERGLASS ARE KNOWN TO

Page 24

30INDOOR AIRFLOW PERFORMANCE FOR 2-5 TON PACKAGE AIR CONDITIONER: RSNL-DIRECT DRIVEDOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)CFM [

Page 25 - GENERAL DATA - RSPL- MODELS

31INDOOR AIRFLOW PERFORMANCE FOR 2-5 TON PACKAGE AIR CONDITIONER: RSPL-DIRECT DRIVE RSPL Indoor Airflow Performance - 230 VoltsCool H

Page 26

32INDOOR AIRFLOW PERFORMANCE FOR 2-5 TON PACKAGE AIR CONDITIONER: RSPL-DIRECT DRIVERSPL Indoor Airflow Performance - 208 VoltsCool Heat 0.1 [.02] 0.2

Page 27

33AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION: RSNL- 208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS C

Page 28 - XX. ELECTRICAL DATA

34AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION: RSPL- 208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS

Page 29 - XXI. AIRFLOW PERFORMANCE

35XXIII. WIRING DIAGRAMSFIGURE 14WIRING DIAGRAM

Page 30 - DIRECT DRIVE

36FIGURE 15WIRING DIAGRAM

Page 31

37FIGURE 16WIRING DIAGRAM

Page 32

38FIGURE 17WIRING DIAGRAM

Page 33

39FIGURE 18WIRING DIAGRAM

Page 34

4II. INTRODUCTIONThis booklet contains the installation and operating instructions for your self-containedair conditioner. There are a few

Page 35 - XXIII. WIRING DIAGRAMS

40FIGURE 19WIRING DIAGRAM

Page 36 - FIGURE 15

41FIGURE 20SYSTEM CHARGE CHARTS2 TON PACKAGE AIR CONDITIONER – 13 & 14 SEER92 - 22904 - 40 - 01OUTDOOR AMBIENT (°F DB)1752002252502753003253503754

Page 37 - FIGURE 16

42FIGURE 21SYSTEM CHARGE CHARTS2.5 TON PACKAGE AIR CONDITIONER – 13 & 14 SEER92-22904- 41 -01°5565758595105115175200225250275300325350375400425450

Page 38 - FIGURE 17

43FIGURE 22SYSTEM CHARGE CHARTS3 TON PACKAGE AIR CONDITIONER – 13 & 14 SEER92-22904-42-01°55657585951051151752002252502753003253503754004254504755

Page 39 - FIGURE 18

44FIGURE 23SYSTEM CHARGE CHARTS3.5 PACKAGE AIR CONDITIONER – 13 & 14 SEER92-22904- 43 -01OUTDOOR AMBIENT (°F DB)5565758595105115175200225250275300

Page 40 - FIGURE 19

45FIGURE 24SYSTEM CHARGE CHARTS4 TON PACKAGE AIR CONDITIONER – 13 & 14 SEER92-22904- 44 -01°556575859510511517520022525027530032535037540042545047

Page 41 - XXIV. CHARGE CHARTS

FIGURE 25SYSTEM CHARGE CHARTS5 TON PACKAGE AIR CONDITIONER – 13 SEER92-22904-57-01INSTRUCTIONS:1. CONNECT PRESSURE GUAGES TO SUCTION AND LIQUID PORTS

Page 42 - FIGURE 21

47FIGURE 26SYSTEM CHARGE CHARTS5 TON PACKAGE AIR CONDITIONER – 14 SEER46FIGURE 25SYSTEM CHARGE CHARTS5 TON PACKAGE AIR CONDITIONER – 13 & 14 SEER9

Page 43 - FIGURE 22

48FIGURE 27SYSTEM CHARGE CHARTS5 TON PACKAGE AIR CONDITIONER – 14 SEER92-22904- 46 -01OUTDOOR AMBIENT (°F DB)55657585951051151752002252502753003253503

Page 44 - FIGURE 23

49TROUBLE SHOOTING CHARTXXV. TROUBLESHOOTINGWARNING!DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURETO SHUT O

Page 45 - FIGURE 24

be done with a mixture of R-410A and air. Leak checking can be performed safelywith nitrogen or a mixture of R-410A and nitrogen.2. Quick Reference G

Page 46 - INSTRUCTIONS:

50FIGURE 27COMFORT ALERT DIAGNOSIS CHARTSINGLE PHASE UNIT Status LED Status LED Description Status LED Troubleshooting InformationGreen “POWER” Mo

Page 47 - FIGURE 25

51FIGURE 28COMFORT ALERT DIAGNOSIS CHARTTHREE PHASE UNIT Status LED Status LED Description Status LED Troubleshooting InformationGreen “POWER” Modu

Page 49 - XXV. TROUBLESHOOTING

6When an abnormal system condition occurs, the Comfort Alert module displays theappropriate ALERT and/or TRIP LED. The yellow ALERT LED will flash a n

Page 50 - SINGLE PHASE UNIT

7The Comfort Alert diagnostics module diagnoses system and electrical problems inthe air conditioning system. Abnormal conditions are indicated by fla

Page 51 - THREE PHASE UNIT

83) Flash Code 4 - Locked RotorCondition: The compressor internal overload trips where the average runtime is less than 15 seconds.Possible causes:Bad

Page 52

9V. EQUIPMENT PROTECTIONIV. (Corrosive Environment)The metal parts of this unit may be subject to rust or deterioration if exposed to a corro-sive env