25M GAS CONTROL
PRODUCT INFORMATION
R-4080
1) Calibration
The regulator is adjusted at the factory to give
the outlet pressure to an orifice as required by
the customer (This is referred to as the set
point). The outlet pressure (B) and the orifice
are selected by the customer to give the desired
flow rate of gas necesary for his application.
This adjustment is made at an inlet pressure (A)
of 7.0" W.C. for natural gas and 14.0" for L.P. gas.
2) Flucuating Inlet Pressure (A)
When the inlet pressure (A) increases, the outlet
pressure (B) starts to increase, but the increasing
force created on the diaphragm causes the stem to
move closer to the seat thereby throttling the flow
and reducing the pressure onto the diaphragm. As
this pressure decreases the stem moves away from
the seat allowing more flow and higher outlet
pressure (B). The outlet pressure, therefore, modu-
lates (high frequency and small amplitude) with
respect to the set point. This is normal operation
for direct acting types of regulators.
general specifications
Regulator Operation
The 25M series gas valve utilizes a direct acting regulator construction to maintain proper outlet gas
pressure for fluctuating inlet pressures. (Refer to Fig. 1)
Outline and Mounting Dimensions
Single Stage Model