White Rodgers 1F85RF-275 Installation Guide Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
10
Press Displayed Press or
Step Button(s) (Factory Default) to select Comments
1 System MS2 SS1, HP2, HP1 Selects Single stage, Multi-stage, or Heat Pump
(Single stage or 2-stage) system configuration
2 System LER (OFF) LER (ON) Selects learn mode OFF or ON
3 System OUTSIDE (OFF) OUTSIDE (ON) Selects OUTSIDE sensor OFF or ON
4 System REMOTE (ON) REMOTE (OFF) Selects REMOTE (indoor) sensor OFF or ON
5 System LOCAL (ON) LOCAL (OFF) Selects LOCAL sensor ON or OFF
6 System CH (0) 1 to 9 Select Receiver frequency offset
7 System PRG 4 PRG 0, PRG 2 Selects Programmable Periods
8 System EMR (ON) EMR (OFF) Selects Energy Management Recovery OFF or ON
9 System CR HEAT COOL (FA) SL Selects Fast or Slow cycle selection
10 System CL (OFF) CL (ON) Selects Compressor Lockout CL OFF or ON
11 System CdL (ON) CdL (OFF) Selects Backlight Display ON or OFF
12 System FA HEAT COOL (ON) FA HEAT COOL (OFF) Selects Fast Second Stage ON or OFF
13 System 0 FLTR 0–1950 (increments of 50) Selects filter replacement run time.0 =Disabled
14 System 0 F 4 LO to 4 HI Selects Temperature Display Adjustment 4 LO 4 HI
(Room Temperature)
15 System 4:00 HOLD 0:00 to 8:00 Selects Temporary Program Override Time
(Increments of 15 minutes) 0:00 =Disabled
16 System F C For C selection
Selects temperature display as F° or C°
17 System LR HEAT (90) LR 62 to LR 89 Selects Limited HEAT range
18 System LR COOL (45) LR 46 to LR 82 Selects Limited COOL range
19 System CA (OFF) CA (ON) Selects Comfort Alert Lock
20 System OFF LOCK ON LOCK Selects Button pad Lockout
21 0 00 LOCK 001 to 999 Selects Buttonpad lockout combination number
Press System to set code
Run Returns to the OFF mode
The configuration menu allows you to set certain thermostat
operating characteristics to your system or personal require-
ments.
Set SYSTEM button to OFF, then simultaneously press
and to enter configuration menu. The display will
show the first item in the configuration menu.
The configuration menu table summarizes the configuration
options. An explanation of each option follows.
Press SYSTEM to change to the next menu item. To exit the
menu and return to the program operation, press RUN. If no
keys are pressed within fifteen minutes, the thermostat will
revert to normal operation.
1) Single Stage, Multi-stage or Heat Pump Configuration
This menu item requires you configure the thermostat to
match your system. Choose your system option from the
table below:
System Type Select Option
Single Stage Heat/Cool systems SS1
Multi-Stage Heat/Cool systems (No Heat Pump) MS2
Heat Pump system, 1 compressor or 1 speed compressor HP1
Heat Pump systems, 2 compressors or 2 speed compressor HP2
The thermostat is factory defaulted to MS2. To select a
different option, press the or key to scroll through
the choices.
THERMOSTAT CONFIGURATION MENU
2) Select Learn Mode On or Off – Selecting LER On
enables the learn mode of the thermostat receiver. Your
thermostat is configured at the factory to recognize the
remote sensor shipped with it. The Learn Mode Option
is used only when required as described in Learn Mode
Option.
3) Selects OUTSIDE sensor OFF or ON – Selecting
OUTSIDE ON enables the thermostat to read a wireless
outdoor temperature sensor that has been configured
for Sensor O in the Learn Mode. This allows the thermo-
stat to display the outdoor temperature reading.
4) Selects REMOTE sensor OFF or ON – Selecting
REMOTE ON allows the thermostat to sense an indoor
remote sensor that has been set-up the Learn mode.
The maximum number of Indoor Remote Sensors is 1
configured to sensor A, B or C.
5) Selects LOCAL sensor ON or OFF – Appears if
Remote is set to ON. Selecting LOCAL ON allows the
thermostat to use the onboard temperature sensor
exclusively or for averaging with the remote sensor
readings. To control temperature using only the indoor
remote sensor temperature(s), use the
or buttons
to select LOCAL OFF.
6) Select Receiver frequency offset – Appears if Remote is
set to ON. This option allows you to select a different
channel than the factory default for communication
between the thermostat and remote sensor. Note: If a
INSTALLER/CONFIGURATION MENU
Press the System button until OFF is displayed, then press the and simultaneously