7
Status LED
Description Comments
 Module has power Supply voltage is present at module terminals
 Comfort Interface en-
ergizing “Y” terminal
to call for cool but the
compressor is not run-
ning
1. Compressor protector is open. Check high head pressure and compressor supply
voltage.
2. Check for open unit power disconnect, circuit breaker or fuses, low pressure switch
if present in system or Compressor contact or has failed open.
3. Broken wire or connector not making contact.

1
1
Long Run Time
Compressor is running
extremely long run
cycles
1. Low refrigerant charge.
2. Evaporator blower is not running. Check blower relay, blower motor capacitor,
motor failure or blockage, wiring and connectors, blower control board, Comfort
Interface wiring for open circuit.
3. Evaporator coil is frozen. Check for low suction pressure, low Comfort Interface

4.
5. Check Comfort Interface sub-base or wiring for short circuit, Comfort Interface
installation (location, level)
6. Faulty TXV (Thermostatic Expansion Valve). Check TXV bulb installation (size,


2
2
System Pressure Trip
Discharge or suction
pressure out of limits or
compressor overloaded
1. High head pressure. Check high pressure switch if present in system, overcharge
with refrigerant, non-condensable in system.
2. Condenser coil poor air circulation (dirty, blocked, damaged)
3. Condenser fan not running. Check fan capacitor, wiring and connectors, motor for
failure or blockage.
4. Return air duct has substantial leakage
5. If low pressure switch present in system, check Flash Code 1 information.

3
3
Short Cycling
Compressor is running

1. Comfort Interface demand signal is intermittent
2. Time delay or control board defective
3. If high pressure switch present go to Flash Code 2 information
4. If low pressure switch present go to Flash Code 1 information

4
4
Locked Rotor
1. Run capacitor has failed.
2. Low line voltage (contact utility if voltage at disconnect is low) check wiring.
3. Excessive liquid refrigerant in compressor. Compressor bearings are seized,
measure compressor oil level.

5
5
Open Circuit
1. Open Outdoor unit power disconnect, circuit breaker, fuse(s). Compressor
contactor failed to open. Check wiring on compressor contactor and between
supply and compressor, contactor failure (burned, pitted), low pilot voltage at
compressor contactor coil.
2. High pressure switch is open and requires manual reset.
3. Unusually long compressor protector reset time due to extreme ambient
temperature.
4. Compressor windings are damaged. Check compressor motor winding resistance.

 6
6
Open Start Circuit
Current only in run
circuit
1. Run capacitor has failed.
2. Open circuit in compressor start wiring or connections. Check wiring and
connectors between supply and the compressor “S” terminal.
3. Compressor start winding is damaged. Check compressor motor winding resistance.

7
7
Open Run Circuit
Current only in start
circuit
1. Open circuit in compressor run wiring or connections. Check wiring and connectors
between supply and the compressor “R” terminal.
2. Compressor run winding is damaged. Check compressor motor winding resistance.

 8
8
Welded Contactor
Compressor always runs
1. Compressor contactor has failed closed
2. Comfort Interface demand signal not connected to module

9
9
Low Voltage Control
Circuit < 17 VAC
1. Control circuit transformer is overloaded
2. Low line voltage (contact utility if voltage at disconnect is low). Check wiring
connections



Control circuit voltage
too low for operation

TROUBLESHOOTING
Note: This is only applicable for systems featuring  (or similar) technology.