OPERATION
OPTION SWITCHES
The option switches on the 50A55-3797 control are used
to determine the length of the heat delay-to-fan-off periods
and cool delay-to-fan-off period. The following tables
shows the time periods that will result from the various
switch positions.
HEAT MODE
In a typical system, a call for heat is initiated by closing the
thermostat contacts. This starts the 50A55 control’s heating
sequence. The inducer blower and optional humidifier are
energized and the ignitor is powered.
This controller has an adaptive algorithm that adjusts
the duration of the ignitor warm-up to extend ignitor life.
Upon initial application of power, the warm-up time is 17
seconds. The ignitor on-time will then be increased or
decreased depending on whether or not flame is achieved.
The warm-up time is limited to a maximum of 21 seconds.
During the first 64 warm-up periods following power-up,
the warm-up time may not be less than 11 seconds.
Upon a call for heat, if the warm-up time has not been
locked, it will be decreased by one second. This reduction
of the ignitor on-time will continue until flame fails to be
achieved (resulting in a retry).
In the event of a retry, the warm-up time will be increased
by one second and locked in at that duration. Once the
warm-up time is locked, it remains fixed until another call
for heat results in a retry, in which case the warm-up time
is again increased by one second and remains locked.
In the event of two successive retry attempts, the warm-up
time will be unlocked and set to 21 seconds. If flame is then
achieved, the warm-up time will begin adapting again with
the next call for heat. If, however, this third attempt fails
to achieve flame, the control will go into system lockout.
At the end of the ignitor warm-up time, both valves in the
gas valve are opened. Flame must be detected within 4
seconds.
If flame is detected, the delay-to-fan-on period begins. After
the delay-to-fan-on period ends, the optional electronic air
cleaner is energized and the circulator fan is energized at
heat speed. When the thermostat is satisfied, the gas valve
is de-energized. After proof of flame loss, the heat delay-
to-fan-off period begins and the inducer blower remains
energized to purge the system for 5 seconds. When the
purge is complete, the inducer blower and humidifier are
de-energized. After the delay-to-fan-off period ends, the
circulator fan and electronic air cleaner are de-energized.
If flame is not detected, both valves are de-energized,
the ignitor is turned off, and the 50A55 control goes into
the “retry” sequence. The “retry” sequence provides a
60-second wait following an unsuccessful ignition attempt
(flame not detected). After this wait, the ignition sequence
is restarted with an additional 1 second of ignitor warm-
up time.
If flame is established for more than 10 seconds after
ignition, the 50A55 controller will clear the ignition attempt
(or retry) counter. If flame is lost after 10 seconds, it will
restart the ignition sequence.
During burner operation, a momentary loss of power of
50 milliseconds or longer will de-energize the main gas
valve. When power is restored, the gas valve will remain
de-energized and a restart of the ignition sequence will
begin immediately.
A momentary loss of gas supply, flame blowout, or a
shorted or open condition in the flame probe circuit will be
sensed within 2.0 seconds. The gas valve will de-energize
and the control will restart the ignition sequence. Recycles
will begin and the burner will operate normally if the gas
supply returns, or the fault condition is corrected.
If the control has gone into system lockout, it may be
possible to reset the control by a momentary power
interruption of one second or longer. Refer to SYSTEM
LOCKOUT FEATURES.
COOL MODE
In a typical system, a call for cool is initiated by closing
the thermostat contacts. This energizes the 50A55
control and the compressor. The cool delay-to-fan-on
period begins. After the delay period ends, the optional
electronic air cleaner is energized, and the circulator
fan is energized at cool speed. After the thermostat is
satisfied, the compressor is de-energized and the cool
mode delay-to-fan-off period begins. After the delay-to-
fan-off period ends, the circulator fan and electronic air
cleaner (optional) are de-energized.
MANUAL FAN ON MODE
If the thermostat fan switch is moved to the ON position,
the circulator fan (heat speed) and optional electronic air
cleaner are energized. When the fan switch is returned
to the AUTO position, the circulator fan and electronic air
cleaner (optional) are de-energized.
COOL "OFF" DELAY
SW1 SECS.
ON 0*
OFF 80
HEAT "OFF" DELAY
SW2 SW3 SECS.
ON OFF 60
ON ON 100*
OFF ON 140
OFF OFF 180
*Factory Setting