INSTALLER/CONFIGURATION MENU
24) Limited Cool Range – This feature provide a minimum
setpoint temperature for cool. The default setting is 45°F. It
can be changed between 46°F and 82°F by pressing the
or button.
25) Select Compressor Off (CO) Feature Using Outdoor
Sensor This feature is applicable only in heat pump
modes and with an outdoor sensor installed and enabled.
When CO is enabled by selecting a temperature >05°F
(-15°C), the thermostat will use the outdoor sensor tem-
perature to determine when to switch to gas heat and shut
down the compressor.
When the outdoor temperature goes below the selected
temperature, the gas heat will begin. Default is 05 (Off or
disabled), but can be set in the range of 06 to 50 using the
or buttons.
Select dF or EA – If CO is set > 05°F (-15°C), select dF
(default) if your system has a fossil fuel (gas or oil) Auxil-
iary heat. Select EA if your system has Electric Auxiliary
heat and you want the compressor to continue to run
while calling for Auxiliary stage.
Select Compressor Delay (Cd) – If dF is selected, after
the auxiliary heat is turned on, the compressor(s) shut
down is delayed for the time selected (in seconds). This
delay is factory set to 60, but can be set in the range of 0
to 99 using
or buttons.
26) Select Auxiliary Off (AO)This feature is applicable only
in heat pump modes and with an outdoor sensor installed
and enabled. Select the temperature that will inhibit the
auxiliary heating stage. As long as the outdoor tempera-
ture is above the setpoint, the auxiliary heat will not turn
on. The default setting is 80, but can be set in the range of
35 to 79. A setting of 80 disables this feature.
27) Select Filter Replacement Reminder and Set Run Time
Select the "Change Filter" reminder On or OFF. If se-
lected On, press MENU to select the time period from 25
to 1975 hours in 25 hours increments. In a typical system,
200 hours (default) of run time is approximately 30 days.
After the selected time of blower operation, the thermostat
will display "Change Filter" as a reminder to change or
clean your air filter. When "Change Filter" is displayed,
press MENU or RUN SCHED button to clear the display
and restart the time to the next filter change.
28) Change UV Lamp – This feature allows the thermostat to
display the words "Change UV Lamp" (Call for Service
of UV bulb) after a set time of UV bulb operation. This is
a reminder to maintain your UV system at optimum level
of operation. When enabled the factory set interval for
"Change UV Lamp" to be displayed is 350 days of UV
bulb operation and can be adjusted in 25 day increments.
This should be adjusted with respect to the bulb's recom-
mended maintenance schedule.
When "Change UV Lamp" is displayed, you can clear it
by pressing MENU.
29) Select Reversing Valve OutputThe O/B option is
factory set at "O" position. This will accommodate the
majority of heat pump applications, which require the
changeover relay to be energized in COOL. If the thermo-
stat you are replacing or the heat pump being installed
with this thermostat requires a "B" terminal, to energize
the changeover relay in HEAT, the O/B option should be
set at "B" position.
OPERATING YOUR THERMOSTAT
If at any time during testing your system does not operate
properly, contact a qualified service person.
Fan Operation
If your system does not have a G terminal connection, skip to
Heating System.
1. Turn on power to system.
2. Press FAN button to select ON. The blower should begin
to operate.
3. Press FAN button to select AUTO. The blower should
stop immediately.
To prevent static discharge problems, touch side of
thermostat to release static build-up before touching
any keys.
NOTE
Check Thermostat Operation
Do not allow the compressor to run unless the com-
pressor oil heaters have been operational for 6 hours
and the system has not been operational for at least
5 minutes.
CAUTION
!
Heating System
1. Press SYSTEM button to select Heat. If the auxiliary
heating system has a standing pilot, be sure to light it.
2. Press
to adjust thermostat setting to 1° above room
temperature. The heat pump system should begin to oper-
ate. The display should show “System On”. However, if
the system configuration is set to HP1 or HP2 and setpoint
temperature display is flashing, the 5 minute compressor
lockout feature is operating (see Configuration menu,
item 11).
3. Adjust temperature setting to 3° above room temperature.
If your system configuration is set at MS2, HP2 or HP1,
the auxiliary heat system should begin to operate and
the display will show “System On +2”.
4. Press to adjust the thermostat below room tempera-
ture. The heating system should stop operating.